Components for Control SystemsQuick Links to Information Below
PDF Documents
Needle Valves for Control SystemsLow profile, high pressure (6,000- and 10,000-PSI) needle valves ideally suited for panel-mounted or other limited space applications. Teflon stem packing provides isolation from the process fluid and prevents contamination and lubrication washout. Standard features include self-aligning swivel pintles to minimize seat scoring, Teflon stem seal, and 316 SS construction to provide maximum compatibility with corrosive fluids. Hydraulic-Pneumatic Interface Valves for Control SystemsThis hydraulic, three-way, two position, normally closed, 316 SS valve permits a low-pressure pneumatic signal to control a high-pressure hydraulic signal. In this unique spool valve design, the usual pilot diaphragm is replaced by a piston. The use of a stainless steel piston and an O-ring or Teflon “cup” seal eliminates failures due to diaphragm leakage and incompatibility of diaphragm with process fluids. The high ratio of hydraulic power pressure to pilot control pressure insures safe operation and positive control under all conditions.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Sizes |
1/4" and 3/8" FNPT |
|
1/4" and 1/2" MNPT |
Maximum operating pressure |
10,000 PSIG |
Operating temperature |
-40° to 450°F |
Seals |
Buna N or Viton |
These right angle relief valves are pressure balanced internally and pressure referenced to atmosphere. This yields insensitivity to downstream pressure and permits the valve to be used as an accurate back-pressure regulator.
| Proof pressure |
20,000 PSIG |
| Minimum burst pressure |
40,000 PSIG |
Design standard |
316 SS |
Operating temperature ranges |
|
|
-40° to 250°F |
|
-20° to 450°F |
Inlet port |
¼" MNPT |
Vent port |
¼" MNPT or FNPT |
| Relief pressure ranges |
100 to 150 PSIG |
|
150 to 250 PSIG |
|
250 to 350 PSIG |
|
350 to 600 PSIG |
|
600 to 900 PSIG |
|
900 to 1,500 PSIG |
|
1,500 to 3,000 PSIG |
|
3,000 to 5,000 PSIG |
|
5,000 to 10,000 PSIG |
Designed to assist personnel operating pneumatic panels with an indication of the presence of control pressures and status in various legs of the pneumatic circuitry. It is intended to be placed in those circuits where there will be an instant indication of loss of pressure.
| Service |
Standard and H2S-CO2 |
| Design standards |
316 SS |
| Fluids |
Air, N2, Natural Gas, H2S-CO2 |
| Operating temperature |
-20° to 450°F |
| Working pressure |
250 PSIG |
| Proof pressure |
500 PSIG |
| Internal/external leakage |
Zero |
| Port sizes |
1/8" and 1/4 " |
Shuttle Valves for Control SystemsThe shuttle valve utilizes a stainless steel ball sealing against an o-ring. Unpredictable breakaway friction usually associated with sliding seals is eliminated through the use of this "“contact seal" principle. The ball offers "frictionless" response to pressure from either inlet and closes the opposite inlet with a bubble-tight seal.
| Service |
Hydraulic or pneumatic |
| Maximum operating pressure |
250 PSIG |
| Proof pressure |
357 PSIG |
| Burst pressure |
500 PSIG |
| Temperature |
-40° to 450°F |
| Design standard |
316 SS |
| O-rings |
Buna N or Viton |

|