| Field Input/Output |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Number of Inputs or Outputs |
32 per node, 64 per module |
 |
|
|
|
|
|
|
|
| |
32 per module |
|
 |
|
|
|
|
|
|
| |
16 per node, 32 per module |
|
|
 |
|
 |
|
|
|
| |
16 per module |
|
|
|
 |
|
 |
|
|
| |
8 per node, 16 per module |
|
|
|
|
|
|
 |
|
| |
8 per module |
|
|
|
|
|
|
|
 |
| Input Type |
32-curr., 32-Volt, 16-RTD, 28 thermocouple, & 1 cold junction temp. |
|
|
|
|
 |
|
|
|
| |
16-curr., 16-Volt, 8-RTD, 14 thermocouple, & 1 cold junction temp. |
|
|
|
|
|
 |
|
|
| Output Type |
Up to 2-Amps continuous, 1-mA leakage open circuit |
|
|
 |
 |
|
|
|
|
| |
0- to 25-mA, isolated and floating |
|
|
|
|
|
|
 |
 |
| |
0- to 5-V, single-ended, ground referenced, 1-KOhm impedance |
|
|
|
|
|
|
 |
 |
| Input Contact Type |
Mechanical contacts or open-collector transistor switch, dry contact type |
 |
 |
|
|
|
|
|
|
| Output Contact Type |
Form “A” solid-state switch dry contact |
|
|
 |
 |
|
|
|
|
| Input Voltage Range |
Current: 0- to 25-mA, Voltage: 0- to 5-V, RTD: 100-Ohm to 1-KOhm, 0.385-Ohms/ºC 3-wire type, all thermocouple types supported, loop power is current limited |
|
|
|
|
 |
 |
|
|
| Output Voltage Range |
Open: 60-Vdc max. circ. working volt., closed: 1-V drop across output |
|
|
 |
 |
|
|
|
|
| Wetting |
Nominal 12- to 24-Vdc per system configuration |
 |
 |
|
|
|
|
|
|
| Open Circuit Voltage |
Open circuit indicates “OFF”/0 |
 |
 |
|
|
|
|
|
|
| Closed Circuit Current |
3-mA controlled constant current, closed circuit indicates “ON”/1 |
 |
 |
|
|
|
|
|
|
| Protection |
Complies with C37-90.1 (IEEE 472) |
 |
 |
 |
 |
 |
 |
 |
 |
| Common Mode Rejection |
Nominal 100-dB |
|
|
|
|
 |
 |
|
|
| Isolation |
3750 VRMS optical isolation |
 |
 |
 |
 |
|
|
 |
 |
| Field Load and Contact Operation Sensing |
Open output switch: leakage curr. of 1-mA through optical coupler allows sensing load presence; Closed output switch: sense voltage shorted out and closed contact state is sensed |
|
|
 |
 |
|
|
|
|
| Voltage Drop in Loop |
5-Vdc |
|
|
|
|
|
|
 |
 |
| Current Output |
4- to 20-mA nominal |
|
|
|
|
|
|
 |
 |
| Offset Zeroing |
0 produces 4-mA ±1 count self-calibrated |
|
|
|
|
|
|
 |
 |
| Gain Error |
4095 ± 5 counts produces 24 mA with no adjustments |
|
|
|
|
|
|
 |
 |
| CPU |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Micro-controller |
Siemens C505C 8-bit processor |
 |
 |
 |
 |
 |
 |
 |
 |
| Processor Speed |
Crystal frequency 16-MHz |
 |
 |
 |
 |
 |
 |
 |
 |
| Watchdog Timer |
Internal |
 |
 |
 |
 |
 |
 |
 |
 |
| Memory Resources |
288-K Flash, 8-K SRAM |
 |
 |
 |
 |
 |
 |
 |
 |
| |
128-Bytes EEPROM |
|
|
|
|
|
|
 |
 |
| Physical Form |
6U rack mount |
 |
|
 |
|
 |
|
 |
|
| |
DIN rail mount |
|
 |
|
 |
|
 |
|
 |
| Points per Module |
64 points on 2 nodes |
 |
|
|
|
|
|
|
|
| |
32 points on 2 nodes |
|
|
 |
|
 |
|
|
|
| |
32 points on 1 node |
|
 |
|
|
|
|
|
|
| |
16 points on 2 nodes |
|
|
|
|
|
|
 |
|
| |
16 points on 1 node |
|
|
|
 |
|
 |
|
|
| |
8 points on 1 node |
|
|
|
|
|
|
|
 |
| Terminations |
Mass termination cable |
 |
|
 |
|
 |
|
 |
|
| |
Screw terminal |
|
 |
|
 |
|
 |
|
 |
| Power Consumption (per node) |
10- to 32-Vdc nominal 0.54-Watts |
 |
 |
 |
 |
 |
 |
|
|
| |
10- to 32-Vdc nominal 1.2-Watts |
|
|
|
|
|
|
 |
 |
| Loop Power (per node) |
160-mA max. |
|
|
|
|
|
|
|
 |
| |
192-mA max. |
 |
 |
|
|
|
|
|
|
| |
320-mA max. (all channels at 20-mA) |
|
|
|
|
|
 |
 |
|
| |
640-mA max. (all channels at 20-mA) |
|
|
|
|
 |
|
|
|
| Dimensions |
Euro 6U height slides into 10.5”x19” rack chassis, 1.5” W |
 |
|
 |
|
 |
|
 |
|
| |
6.5”L x 3.3”W x 2.8”H |
|
 |
|
 |
|
 |
|
 |
| LED Status Indicators |
Input status one per unit |
 |
 |
|
|
|
|
|
|
| 64 |
32 |
| |
Display of desired logic and current output state for each channel |
|
|
 |
 |
|
|
|
|
| |
Comm. channel, I/O module PCM activity, & diagnostic/fault indication |
 |
 |
 |
 |
 |
 |
 |
 |
| Environmental |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Oper./ Storage Temp. |
-40º to +85ºC (-40º to +185ºF) |
 |
 |
 |
 |
 |
 |
 |
 |
| Humidity |
100% non-condensing |
 |
 |
 |
 |
 |
 |
 |
 |
| Conformal Coating |
Standard |
 |
 |
 |
 |
 |
 |
 |
 |
| Communications |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Sync |
PCM sends marker message once-per-second which synchronizes I/O modules to the same 1-ms mark |
 |
 |
 |
 |
 |
 |
 |
 |
| Dual CAN Comm. |
Two CAN network channels are accessible to the I/O module |
 |
 |
 |
 |
 |
 |
 |
 |
| User Configuration |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Accessibility |
All user configurable parameters specified are accessible via CAN communications and are accessible from the host level |
 |
 |
 |
 |
 |
 |
 |
 |
| Debounce |
User selects how many contiguous samples must agree before recognition of change |
 |
 |
|
|
|
|
|
|
| COS Report |
User selects which edge of COS produces CAN message |
 |
 |
|
|
|
|
|
|
| Accumulator Count |
User selects which edge produces an accumulator count |
 |
 |
|
|
|
|
|
|
| Accumulator Report |
User selects a pre-scale value and a modulus |
 |
 |
|
|
|
|
|
|
| Signal Processing |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Sampling Rate |
Digital or analog inputs are sampled each 1-ms |
 |
 |
|
|
 |
 |
|
|
| Resolution |
24-bit |
|
|
|
|
 |
 |
|
|
| |
12-bit |
|
|
|
|
|
|
 |
 |
| Input Filtering |
60-Hz notch @ 7.5 samples/ second |
|
|
|
|
 |
 |
|
|
| Input Contact Debounce |
Configurable on per point basis, can set up to 250-ms |
 |
|
|
|
|
|
|
|
| Input Contact Extraneous Transitions |
Debounce characteristic is user configurable per point, defines number of contiguous samples that must agree before new state of input accepted |
|
 |
|
|
|
|
|
|
| Debounce Conf. Status Signals |
Up to 250-ms can be set for very unstable sources |
|
|
|
|
|
|
|
|
| Debounce Upper Freq. Cut-Off |
When conf. with zero debounce max. rate-per-point is 250-Hz, 50% duty cycle |
 |
 |
|
|
|
|
|
|
| Change of State (COS) Reporting |
User configurable for reporting change immediately for: |
 |
 |
|
|
|
|
|
|
| OFF to ON; ON to OFF, BOTH, NEITHER |
| Accumulator - 16-bit, 24-bit with Pre-scale |
Each point user configurable for counting input changes: |
 |
 |
|
|
|
|
|
|
| Max. rate of 250-Hz |
| OFF to ON; ON to OFF; BOTH; NEITHER |
| Accumulator Report |
Each accumulator has conf. pre-scale & modulus values |
|
 |
|
|
|
|
|
|
| Accumulator Pre-scale |
A configurable pre-scale value allows for dividing the raw counts by 1 to 256 before they appear in the accumulator |
|
 |
|
|
|
|
|
|
| Latched Output |
Maintains the last commanded status while power is applied |
|
|
 |
 |
|
|
|
|
| |
When power is interrupted & returned, module ladder logic can be conf. for returning to last or a pre-defined default state |
|
|
|
 |
|
|
|
|
| Retentive Output |
Output state is retained/reset as configured in module fail sequence logic when power is lost |
|
|
 |
 |
|
|
|
|
| Pulse Output |
If not conf. for hardware SBE, each point is conf. for activation between 10- to 655,350-ms |
|
|
 |
 |
|
|
|
|
| Duty Cycle Output (PWM) |
Each point is conf. for activation in repeating cycles & duration from 10- to 10,000-ms |
|
|
 |
 |
|
|
|
|
| Output Update Rate |
All outputs are updated every 10-ms |
|
|
|
|
|
|
 |
 |
| Report Processing |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Report by Exception |
Data reported when input exceeds per point conf. dead band |
|
|
|
|
 |
 |
|
|
| Report on High High, High, Low, & Low Low |
Exception reports are generated when crossing any of these four thresholds |
|
|
|
|
 |
 |
|
|
| Periodic Report |
Data reported on min. interval conf. by user regardless of data change |
 |
 |
|
|
 |
 |
|
|
| Rate Processing |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Rate Report |
With the accumulator report, time between pulses & number of pulses-per-second are each reported |
|
 |
|
|
|
|
|
|
| Alarm Report Accumulator Rate Maximum |
Maximum frequency or minimum period |
|
 |
|
|
|
|
|
|
| Alarm Report Accumulator Rate Minimum |
Minimum frequency or maximum period |
|
 |
|
|
|
|
|
|
| Module Failsafe Logic |
Digital Input |
Digital Output |
Analog Input |
Analog Output |
| DIM1-6U |
DIM1-D |
DOM1-6U |
DOM1-D |
AIM1-6U |
AIM1-D |
AOM1-6U |
AOM1-D |
| Control Sequence on Comm Failure |
DOM loss of comm. less than 14 sec., then alarm & pre-programmed shutdown |
|
|
 |
 |
|
|
|
|