CAC EXS-1000 Remote Terminal Unit (RTU)Quick Links to Information Below
PDF Documents eP’s CAC EXS-1000 Extreme Service Remote Terminal Unit (RTU) series is for use in automating oil and gas production wells, and other general purpose applications requiring small to medium I/O point counts. The CAC EXS-1000 electronic circuit boards are conformally coated for protection in extremely corrosive, humid and temperate environments.
eP’s CAC EXS-1000 is a cost effective production automation controller designed for simple applications as a standalone unit, or for more complex applications that involve control, communications, and alarming. Start-up is easy using the keypad/liquid crystal display or Windows™ based configuration management software. No special programming knowledge is required to apply the automatic alarm based control functions. The CAC EXS-1000 is designed for easy communications to host computers and DCS systems using either Modbus™ RTU, Modbus ASCII or CAC’s 8500 protocol. The basic RTU measures 8” x 7.5” x 2.5” and may be mounted stand-alone on any control panel or optionally packaged in a NEMA 4 enclosure for outdoor service. Low power requirements make the CAC EXS-1000 ideal for solar power applications. Base unit power consumption is 2.5 watts @ 12 Vdc.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Software Specifications |
|
Control | Two PID control loops, output calculated every second |
Serial Communication Interface | Two RS-232 asynchronous serial ports expandable up to four or six |
Communications Protocols | Modbus ASCII, Modbus RTU, or CAC 8500 |
Communications Options | Bell Model 103, 202, or 212 modem. Digital radio with integral modem (450- or 900-Mhz). |
Hardware Specifications |
|
Analog Inputs | Eight (one analog input can be jumpered for direct 100 Ohm platinum RTD input) |
Range | Nominal 0 to 5 Vdc, 1 to 5 Vdc, 0 to 25 mA or 4 to 20 mA (jumper selectable) |
Resolution | 12 Bit, unipolar |
Accuracy | Current inputs ±0.1% of full scale, voltage inputs ±0.1% of full scale (including linearity, hysteresis, repeatability, and resolution) |
Temperature Coefficient | ±0.01% of full scale/degree F |
Analog Outputs | Two |
Range | 0 to 25 mA or 4 to 20 mA |
Resolution | 12 Bit, unipolar |
Accuracy | ±0.1%, firmware calibratable to ±0.1% (including linearity, hysteresis, repeatability, and resolution) |
Digital Inputs | Eight inputs @ 4 to 32 Vdc, 2 Hz maximum, 2 mA current limited (firmware filtered) |
Optional | Turbine meter prescaler accepts up to 5 Khz signals from turbine meter |
Digital Outputs | Eight outputs @ 0.5 Amp continuous, 6 Amp pulsed, 32 Vdc maximum |
Real Time Clock | Accurate to within ±1 minute/ month over operating temperature range |
Data Ports | Two RS-232 asynchronous serial ports (1 for MMI, 1 for 300 to 19.2 KBaud telecommunications) |
Expansion ports provide RS-232 or RS-485 interface to external instruments and/or controllers |
|
Operating Range | -40° to +85°C, 0-95% relative humidity (non-condensing) |
Power Requirements | 8 to 32 Vdc @ 2.5 Watts average |
Options | 110 Vac, 50/60 Hz input with one day battery (12 Vdc) backup, 0° to 60°C operation (assumes 1 Amp maximum load) |
24 Vdc battery charging and backup for AC or solar powered units |
|
12/24 Vdc DC to DC converter, used for 4 to 20 mA transmitters when battery backup is 12 Vdc |
|
220 Vac, 50/60 Hz operation for AC input units |
|
Local Display | 2 x 24 LCD (-20° to +70°C), optional with 20-key keypad |
Overvoltage/Transient Protection | All inputs/outputs and power supply devices provided with surge protection to ANSI/IEEE C37-90.1-1989 (IEEE Std. 472-1974) |

|
Copyright © 2007 eProduction Solutions, Incorporated. All rights reserved. |
![]() |