Specifications of SP350 Series Programmable Logic Controllers
P350 (5209 controller board only)
| Controller |
| Processor |
CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
Two microcontroller co-processors, 20 MHz clock |
| Memory |
4 Mb SRAM, 16 Mb flash ROM |
| Non-Volatile |
CMOS SRAM with lithium battery retains contents for two years with no power |
| Datalog Capacity |
465 k words |
| I/O |
| Analog Inputs |
Five, user selectable 0 to 10 V (15-bit) or 0 to 20 mA (14-bit)
One, 0 to 32.7 Vdc (15-bit) |
| Analog Outputs |
Standard: none
Two, 0 to 20 mA/4 to 20 mA (12-bit) with optional 5305 |
| Digital I/O |
Eight, user selectable as dry contact inputs or open drain outputs |
| Counter Inputs |
One, 0 to 10 Hz (dry contact)
Two, 0 to 10 kHz (turbine or dry contact) |
| Communications |
| Serial Port COM1 |
RS-485 port, two-pole removable terminal block, two-wire, half duplex |
| Serial Port COM2 |
RS-232 port, eight-pin modular RJ45 jack, full or half duplex RS-232, or RS-485 port, two-wire, half duplex |
| Serial Port COM3 |
RS-232 port, eight pin modular RJ45 jack, half duplex with RTS/CTS control and Vision OIT power control |
| Baud Rates |
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 |
| Serial Protocols |
Modbus RTU, Modbus ASCII, DNP 3, DF1 |
| Serial Protocol Modes |
Slave, master, master/slave, store and forward |
| Ethernet Port |
RJ45, 10/100BaseT |
| Ethernet Protocols |
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP |
| Network Protocols |
IP, ARP, TCP, TFTP, UDP and ICMP |
| USB Host Port |
USB 2.0 compliant “A” type receptacle, provides up to 100 mA at 5 V |
| USB Peripheral Port |
USB 2.0 compliant “B” type receptacle |
| Wireless1 |
Spread spectrum radio at 900 MHz2 and 2.4 GHz2 |
| General |
| I/O Terminations |
Six and twelve-pole removable terminal blocks, 12 to 22 AWG, 15 A contacts |
| Dimensions |
8.40 in. (213 mm.) wide, 5.00 in. (127 mm.) high, 1.80 in. (45 mm.) deep |
| Packaging |
Corrosion resistant zinc-plated steel with white enamel paint |
| Environment |
5% RH to 95%, non-condensing, -40° to 158°F (-40° to 70°C) |
| Power Input |
11 to 30 Vdc, 12 mW at 12 V during sleep
510 mW at 12 V during normal operation, 32 MHz, LEDs off, no expansion, LAN and USB disabled
275 mW at 12 V during normal operation, 8 MHz, LEDs off, no expansion, LAN and USB disabled (reduced power mode)
1.2 W at 12 V during normal operation, 32 MHz, LEDs off, no expansion, LAN enabled and USB disabled
Add 25 to 100 mW when enabling the LEDs
12 W at 24 V maximum, 5 V supply fully loaded and Vloop on and boosted, fully loaded |
| Voltage Converter |
12 to 24 Vdc |
| Warranty |
Three years on parts and labor |
| Certifications |
| UL Class 1, Division 2, Groups A, B, C and D for use in Hazardous Locations |
1Available only with optional integrated wireless modules or with stand-alone wireless modules.
2Not applicable in all countries.
P357 (5209 controller board and integrated 5606 I/O board)
| Controller |
| Processor |
CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
Two microcontroller co-processors, 20 MHz clock |
| Memory |
4 Mb SRAM, 16 Mb flash ROM |
| Non-Volatile |
CMOS SRAM with lithium battery retains contents for two years with no power |
| Datalog Capacity |
465 k words |
| I/O |
| Analog Inputs |
Five, user selectable 0 to 10 V (15-bit) or 0 to 20 mA (14-bit)
One, 0 to 32.7 Vdc (15-bit)
Eight, 0 to 20 mA/4 to 20 mA/0 to 5 V/0 to 10 V (15-bit) software configurable |
| Analog Outputs |
Standard: none
Two, 0 to 20 mA/4 to 20 mA (12-bit) with optional 5305 on 5209 controller board
Two, 0 to 20 mA/4 to 20 mA (12-bit) with optional 5305 on 5606 I/O board |
| Digital I/O |
Eight, user selectable as dry contact inputs or open drain outputs
Thirty two, 12/24 V, 48 V, 115/125 V, 240 V digital inputs
Sixteen, dry contact relay outputs |
| Counter Inputs |
One, 0 to 10 Hz (dry contact)
Two, 0 to 10 kHz (turbine or dry contact) |
| Communications |
| Serial Port COM1 |
RS-485 port, two-pole removable terminal block, two-wire, half duplex |
| Serial Port COM2 |
RS-232 port, eight-pin modular RJ45 jack, full or half duplex RS-232, or RS-485 port, two-wire, half duplex |
| Serial Port COM3 |
RS-232 port, eight pin modular RJ45 jack, half duplex with RTS/CTS control and Vision OIT power control |
| Baud Rates |
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 |
| Serial Protocols |
Modbus RTU, Modbus ASCII, DNP 3, DF1 |
| Serial Protocol Modes |
Slave, master, master/slave, store and forward |
| Ethernet Port |
RJ45, 10/100BaseT |
| Ethernet to Serial Gateway1 |
RJ45, 10BaseT |
| Ethernet Port Protocols |
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP |
| Network Protocols |
IP, ARP, TCP, TFTP, UDP and ICMP |
| USB Host Port |
USB 2.0 compliant “A” type receptacle, provides up to 100 mA at 5 V |
| USB Peripheral Port |
USB 2.0 compliant “B” type receptacle |
| Wireless1 |
Spread spectrum radio at 900 MHz2 and 2.4 GHz2 |
| Power Input |
| 5209 Controller Board |
11 to 30 Vdc, 12 mW at 12 V during sleep
510 mW at 12 V during normal operation, 32 MHz, LEDs off, no expansion, LAN and USB disabled
275 mW at 12 V during normal operation, 8 MHz, LEDs off, no expansion, LAN and USB disabled (reduced power mode)
1.2 W at 12 V during normal operation, 32 MHz, LEDs off, no expansion, LAN enabled and USB disabled
Add 25 to 100 mW when enabling the LEDs
12 W at 24 V maximum, 5 V supply fully loaded and Vloop on and boosted, fully loaded |
| 5606 I/O Module |
11 to 30 Vdc, 600 mA (max) at 5 V required from 5209 controller board
12 mA plus analog outputs |
| General |
| I/O Terminations |
Five, six, nine, ten and twelve-pole removable terminal blocks, 12 to 22 AWG, 15 A contacts |
| Dimensions |
8.40 in. (213 mm.) wide, 6.13 in. (155 mm.) high, 2.80 in. (72 mm.) deep |
| Packaging |
Corrosion resistant zinc-plated steel with white enamel paint |
| Environment |
5% RH to 95%, non-condensing, -40° to 158°F (-40° to 70°C) |
| Voltage Converter |
12 to 24 Vdc |
| Warranty |
Three years on parts and labor |
| Certifications |
| UL Class 1, Division 2, Groups A, B, C and D for use in Hazardous Locations |
1Available only with optional integrated wireless modules or with stand-alone wireless modules.
2Not applicable in all countries.
|
 |