Specifications of SS 4102 Modbus® Multivariable Transmitter
Span and Range Limits for Differential and Absolute Pressure
| Features |
Differential Pressure |
Absolute Pressure |
| Inches of H2O |
kPa |
PSIa |
MPa |
| A |
0.5 to 30 |
0.12 to 7.5 |
1 to 100 |
0.007 to 0.7 |
| B |
2 to 200 |
0.50 to 50 |
3 to 300 |
0.021 to 2.1 |
| C |
10 to 840 |
2.50 to 210 |
3 to 300 |
0.021 to 2.1 |
| D |
2 to 200 |
0.50 to 50 |
30 to 1500 |
0.21 to 10 |
| E |
3 to 300 |
0.75 to 75 |
30 to 1500 |
0.21 to 10 |
| F |
10 to 840 |
2.50 to 210 |
30 to 1500 |
0.21 to 10 |
| Features |
| Optional Analog Output |
0 to 20 mA, 12-bit |
| Optional PID Controller |
Fully configurable control of analog output relative to any measured variable |
| LCD Interface1 |
Two button control, 2-line interface with 13 characters |
| Communications |
| Serial port |
RS232/RS485 configurable, 1200 to 38400 baud |
| Serial protocol |
Modbus RTU |
| Ethernet port2 |
10BaseT, terminal block connection |
| Ethernet protocols2 |
Modbus/TCP, Modbus/UDP, Modbus RTU in TCP, Modbus RTU in UDP |
| Accuracy and Stability |
Differential and absolute pressure
accuracy |
±0.05% of span (for spans ≥10% of URL)
±(0.005) x (URL/span)% of span (spans <10% URL)3 |
| Process temperature accuracy (°F/°C) |
±0.5 (0.28), not including RTD uncertainties |
| Stability |
<±0.05% of URL per year over five years |
| Static pressure effect |
ZERO Shift ±0.05% of URL, SPAN Shift ±0.1% of reading for 1000 psi (7 MPa) |
| Ambient temperature effect |
Total effect for a 100°F (55°C) change for absolute and differential pressure is:
Digital Output: ±(0.0625% URL + 0.125% Reading) |
| Physical |
| Power |
9 to 30 Vdc, 225 mW with LAN (60 mW with serial communications) |
| Mass (lb./kg) |
7.8 (3.5) without process connectors |
| Certifications |
c(CSA)us Explosion proof, Class I, Division 1, Groups B, C and D Hazardous Locations
c(CSA)US Class I, Division 2, Groups A, B, C and D Hazardous Locations
IECEx to Exd IIC T6
ATEX to EEx d IIC T6
RTD connections rated non-incendive in Division 2 areas |
1Button control disabled when setup for calibration through a controller using RealFLO software
2Available without an Ethernet port
3Accuracy stated includes the effects of linearity, hysteresis and repeatability
|
 |